Shandong Sinoguan Industrial Equipment Co., Ltd. is a high-tech enterprise in Jinan City, mainly engaged in gas detection, safety protection, imported pneumatic import valves and other high-end industrial equipment. The company is rooted in Qilu and faces the whole country and the world. It provides safe, reliable and high-quality equipment for customers such as energy and chemical machinery manufacturing, coal coking, gas transportation, pesticides and pharmaceuticals. The following is the relevant knowledge you need to know before installing flammable alarm equipment
. The explosion-proof category, level, and group of the instrument combustible gas alarm must be selected to meet the requirements of the category, level, and group of the explosive gas mixture on site. It must not be used in an environment that exceeds the environment allowed by the explosion-proof mark, otherwise it will not have an explosion-proof effect. When selecting instruments, you should consider that the manufacturer's regular products are technologically advanced, sensitive and reliable, and meet the corresponding environmental requirements.
. Periodic calibration
Calibration instruments must use standard gas certified by the measurement department that matches the gas being measured. Inject the zero point gas to make the instrument display the concentration as %, then inject standard gases of different concentrations and adjust the instrument to the standard indication value after the indication value stabilizes. Other indicators should comply with the requirements in the corresponding national metrology verification regulations. The calibration period generally does not exceed one year. It should also be noted that if you need to disassemble and debug during the calibration process, you must wear a portable instrument to detect the presence of flammable gases in the surrounding environment and use an explosion-proof walkie-talkie to guide debugging.
. Installation quantity
For large and medium-sized places where there is a possibility of flammable gas leakage, one detection point should be set up every (~) apart according to relevant regulations. Testing points should also be set up for relatively closed small spaces (such as pump rooms and bottle storage rooms). When the gas types in the on-site environment are complex, the number and model of detectors should also be increased accordingly. If the detector does not comply with the on-site environment, it will not only be unable to detect the concentration of ambient gases, but may also easily cause detector failure and damage.
. Installation environment
For detector probes installed in the open air, temperature and humidity factors must be considered to ensure that the ambient temperature and humidity comply with the instrument's instructions for use. The place where the instrument is installed should also consider the impact of halogen compounds on the instrument. Otherwise, the sensitivity of the combustible gas detector will be reduced, the service life will be shortened, and the instrument will even lose its detection function.
. Regular inspection
For instruments with self-test function, the self-test button should be pressed once a week to check whether the indicating and alarm system is normal. Perform a visual inspection once a week to check the connection parts, movable parts, displays and control knobs. Check the fault light. Explosion-proof seals and fasteners, check whether the probe is blocked, check for waterproofing, etc. The author believes that it is inappropriate to directly use the lighter gas to contact the detector probe to test the reliability of the instrument. This can easily lead to damage to the gas detector probe, reduced sensitivity or malfunction of the detector.
. Installation location
The height of the installation location of the combustible gas alarm should depend on the density of the gas being measured. The detector probe should be installed above the leak point for gases being measured that have a density greater than air. The gas detector probe should be installed below the leak point and about 1.5 meters above the ground. If the density of the gas to be measured is similar to that of air, the detector probe should be as close to the leak point as possible. The installation height of the open-air probe should also be selected based on the density of the gas being measured. Special attention should be paid to the fact that the detector probe should be installed on the downwind side of the dominant wind direction. After the detector probe is installed and debugged, a breathable and waterproof cover must be installed to prevent rainwater from entering and damaging the probe. The breathable and waterproof cover should be cleaned regularly to ensure that the gas being measured normally enters the detector probe.
Shandong Snow Crown Industry proposes a complete set of installation solutions for flammable/toxic gas detection to eliminate your health risks. Hot selling nationwide, inquiries welcome.